Ground Fault Interrupter接地断路器
Ground fault interrupters are designed to protect from electrical shock by interrupting a household circuit when there is a difference in the currents in the "hot" and neutral wires. Such a difference indicates that an abnormal diversion of current from the "hot" wire is occuring. Such a current might be flowing in the ground wire, such as a leakage current from a motor or from capacitors. More importantly, that current diversion may be occurring because a person has come into contact with the "hot" wire and is being shocked. When a circuit is functioning normally, all the return current from an appliance flows through the neutral wire, so the presence of a difference between "hot" and neutral currents represents a malfunction which in some circumstances could produce a dangerous or even lethal shock hazard. 接地保护装置是通过在“火线”和中性线电流不一致时切断家庭电路来防止电击的。这种电流差异表明电流可能异常地从“火线”分流到地线,例如电机或电容器的漏电流。更重要的是,这种电流分流可能是因为有人接触了“火线”而被电击。当电路正常工作时,所有电器的回流电流都通过中性线返回,因此“火线”和中性线电流之间的差异表示一种故障,这种故障在某些情况下可能产生危险甚至致命的电击隐患。
![]() The "hot" and neutral wires are passed through the sensing coil so that the currents in the two wires at any instant are traveling in opposite directions, giving a net zero current in the coil if the two currents are exactly equal. Since a current-carrying wire produces an AC magnetic field external to the wire, a non-zero current would induce a voltage in the sensing coil. The sensing coil is wound longitudinally to capture more of the wire's magnetic field and therefore be a more sensitive net current detector. Even so, the difference that it is supposed to detect is quite small. The GFI is designed to trip when there is more than 5 milliamperes of leakage current out of the normal pathway. The neutral return would then have 5 mA less current than the "hot" wire, but that might be out of a 20A load. So the circuit would have to detect a 0.025% deviation from 20A return current. Fortunately, comparator circuits such as an op-amp comparator are quite capable of detecting such differences. The voltage in the sensor coil is rectified and applied to the input of the sensitive comparator. The comparator activates a trip coil which opens both the "hot" and neutral wires. If all circuits were wired with correct polarity, opening the "hot" wire would be sufficient, but since it is not uncommon for them to be accidentally wired backward, it is prudent to interrupt both leads. ‘热’线和中性线通过传感线圈,使得两根导线在任何时刻的电流方向相反,如果两电流恰好相等,则线圈中的净电流为零。由于带电流的导线会产生外部的交变磁场,非零电流会在传感线圈中感应出电压。传感线圈纵向绕制以捕捉更多的导线磁场,因此成为更灵敏的净电流检测器。尽管如此,它所要检测的差异仍然非常小。GFI 设计为在正常路径外有超过 5 毫安漏电流时触发。中性回路电流将比‘热’线电流少 5 mA,但可能来自 20A 的负载。因此电路必须检测 20A 回路电流的 0.025% 差异。幸运的是,比较器电路,如运算放大器比较器,完全有能力检测到这样的差异。传感器线圈中的电压被整流并施加到敏感比较器的输入端。比较器激活触发线圈,断开‘热’线和中性线。如果所有电路都正确极性连接,断开‘热’线就足够了,但由于它们有时会被错误地反向连接,因此中断两条线路是明智的。
It is common household practice to wire several receptacles on a given circuit. A single GFI at the circuit panel will protect the entire collection of receptacles since a difference between "hot" and neutral current at any one of them will cause a difference at the GFI. A single GFI at one receptacle would not protect the entire circuit. 在家庭中,通常会将多个插座连接到同一电路中。电路面板上的一个GFI(接地故障断路器)可以保护所有这些插座,因为如果任何一个插座的“火线”和中性线电流之间存在差异,这种差异会传递到GFI上,从而触发保护。而仅在一个插座上安装一个GFI则无法保护整个电路。
Because of the great sensitivity of the detection of current differences, GFIs are prone to nuisance tripping in certain applications. A rather common practice in some areas is to have a freezer on the carport, and carport receptacles are sometimes wired with GFIs. Under moist conditions you can sometimes get enough leakage current to trip the GFI, and persons come back to find their freezer thawed out. A necessary safety precaution in bathrooms and near pools, they are sometimes quite troublesome in outdoor applications where reliable power is needed. John de Armond has a good discussion of other circumstances which lead to nuisance tripping, particularly with campers and recreational vehicles. 由于电流差的高灵敏度,GFIs在某些应用中容易引发误动作。在某些地区,一种常见的做法是在车棚内安装一个冰箱,而车棚的插座有时会安装GFIs。在潮湿条件下,有时可以产生足够的漏电流以触发GFI,人们回来时会发现冰箱被解冻了。在浴室和靠近游泳池的地方,这是必要的安全预防措施,但在需要可靠电源的户外应用中,它们有时会带来相当多的麻烦。John de Armond对导致误动作的其他情况有很好的讨论,特别是针对露营者和休闲车辆。
|
Index Practical circuit concepts 索引 实用电路概念 | ||
|
Go Back
返回 |